Background During the COVID-19 pandemic, aerosol spread of SARS-CoV-2 has been a major problem in healthcare facilities, resulting in increased use of supplementary HEPA filtration to mitigate transmission. We report here a natural experiment that occurred when an air filtration unit (AFU) on an inpatient ward for older people was accidentally switched off.
Aim To assess aerosol transport within the ward and determine whether the AFU reduced particulate matter (PM) levels in the air.
Methods Time-series PM, CO2, temperature and humidity data (at 1 minute intervals) was collected from multiple sensors around the ward over two days in August 2021. During this period, the AFU was accidentally switched off for approximately 7 hours, allowing the impact of the intervention on particulates (PM1-PM10) to be assessed using a Mann-Whitney test. Pearson correlation analysis of the PM and CO2 signals was also undertaken to evaluate the movement of airborne particulates around the ward.